Integrated Rectifier Technologies Inc.

Rectifiers | Control Panels

  • Home
  • Company
    • Contact IRT
  • Products
    • Rectifiers
      • Rectifier Coding
      • Rectifier Standard DC Output Ratings
    • Junction Boxes
      • Junction Box Coding
    • Sacrificial Anode Test Station
    • Replacement Parts
    • Limited Warranty
    • Quality
  • Technical Info
    • Rectifier AC Input Current Calculator (MS Excel Download)
    • Rectifier Safety
    • Rectifier Request Guidelines and Product Model Limitations
    • Installation Guidelines for Potential Controlled Rectifiers
    • Enclosure Material Considerations and Rating Definitions
      • National Electrical Manufacturers Association (NEMA) Enclosure Rating Definitions
      • Underwriters Laboratories Inc. (UL) Enclosure Rating Definitions
      • Canadian Standards Association (CSA) Enclosure Rating Definitions
  • Services
    • Product Design
    • Product Support
    • Product Repair
    • Product Training
    • Third-Party Equipment Installation
You are here: Home / Technical Info / Enclosure Material Considerations and Rating Definitions / National Electrical Manufacturers Association (NEMA) Enclosure Rating Definitions

National Electrical Manufacturers Association (NEMA) Enclosure Rating Definitions

Print Friendly, PDF & Email

Type 1

Indoor use to provide a degree of protection against contact with the enclosed equipment; in locations where unusual service conditions do not exist.

Type 2

Indoor use to provide a degree of protection against contact with the enclosed equipment and against limited amounts of falling water and dirt.

Type 3

Indoor or outdoor use to provide a degree of protection against windblown dust, rain and sleet; undamaged by the formation of ice on the enclosure (not sleet proof).

Type 3R

Indoor or outdoor use to provide a degree of protection against falling rain and sleet; undamaged by the formation of ice on the enclosure.

Type 3S

Indoor or outdoor use to provide a degree of protection against windblown dust, rain and sleet; provides for operation of external mechanisms when ice laden.

Type 4

Indoor or outdoor use to protect the enclosed equipment against splashing water, seepage of water, falling or hose-directed water, and severe external condensation; these enclosures are sleet resistant but not sleet proof.

Type 4X

Indoor or outdoor use to provide a degree of protection against corrosion, windblown dust and rain, splashing water, and hose-directed water; undamaged by the formation of ice on the enclosure.

Type 5

Indoor use to provide a degree of protection against dust, falling dirt, and dripping non-corrosive liquids.

Type 6

Indoor or outdoor use to provide a degree of protection against the entry of water during occasional temporary submersion at a limited depth.

Type 6P

Indoor or outdoor use to provide a degree of protection against the entry of water during prolonged submersion at a limited depth.

Type 7

For use in indoor locations classified as Class I, Groups A, B, C and D, as defined in the National Electrical Code.

Type 8

For use in indoor or outdoor locations classified as Class I, Groups A, B, C and D, as defined in the National Electrical Code – oil immersed.

Type 9

For use in indoor locations classified as Class II, Groups E, F and G, as defined in the National Electrical Code.

Type 10

Mining enforcement safety administration approved.

Type 11

Indoor use to provide, by oil immersion, a degree of protection to enclosed equipment against corrosive effects of liquids and gases.

Type 12

Indoor use to provide a degree of protection against dust, falling dirt and dripping non-corrosive liquids No knockouts.

Type 12K

Indoor enclosure with knockouts to provide a degree of protection against dust, falling dirt and dripping
non-corrosive liquids other than at knockouts.

Type 13

Indoor use to provide a degree of protection against lint, dust, seepage, external condensation and spraying of water, oil and noncorrosive coolant.